Forster South Asia customer 2x250kw Francis turbine has completed the installation and successfully connected to the grid

Forster South Asia customer 2x250kw Francis turbine has completed the installation and successfully connected to the grid
413181228
The following is the detailed parameter information of the 2X250 kW Francis Turbine Generator Unit:
Water Head:                                      47.5 m
Flow rate:                                          1.25³/s
Installed Capacity:                             2*250 kw
Turbine:                                              HLF251-WJ-46
Unit Flow( Q11):                                 0.562m³/s
Unit Rotating Speed(n11 ):                 66.7rpm/min
Max Hydraulic Thrust (Pt ):                 2.1t
Rated Rotating Speed( r ):                 1000r/min
Model Efficiency of Turbine ( ηm ):    90%
Max Runway Speed (nfmax ):           1924r/min
Rated Output (Nt ):                            250kw
Rated Discharge (Qr)                        0.8m3/s
Rated Efficiency of Generator (ηf):   93%
Frequency of Generator( f):              50Hz
Rated Voltage of Generator (V ):      400V
Rated Current of Generator (I ):        541.3A
Excitation :                                         Brushless Excitation
Connection Way                                Direct Connection
250KW francis turbine1

250KW francis turbine7

250KW francis turbine4
Due to the influence of covid-19, Forster engineers can only guide the installation and commissioning of hydraulic generators online. Customers highly recognize the ability and patience of Forster engineers and are very satisfied with our after-sales service.
20220414160806
20220414160019


Post time: Apr-14-2022

Send your message to us:

Write your message here and send it to us